range |
TeSys |
|
---|---|---|
product name |
TeSys GV2 |
|
device short name |
GV2ME |
|
device application |
Motor |
|
trip unit technology |
Thermal-magnetic |
poles description |
3P |
|
---|---|---|
network type |
AC |
|
utilisation category |
AC-3 conforming to IEC 60947-4-1 Category A conforming to IEC 60947-2 |
|
network frequency |
50/60 Hz conforming to IEC 60947-4-1 |
|
fixing mode |
35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate) |
|
operating position |
Any position |
|
breaking capacity |
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service short-circuit breaking capacity |
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
control type |
Push-button |
|
[In] rated current |
0.16 A |
|
thermal protection adjustment range |
0.1…0.16 A |
|
magnetic tripping current |
1.5 A |
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ith] conventional free air thermal current |
0.16 A conforming to IEC 60947-4-1 |
|
[Uimp] rated impulse withstand voltage |
IEC 60947-2 6 kV |
|
power dissipation per pole |
2.5 W |
|
mechanical durability |
100000 cycles |
|
electrical durability |
100000 cycles for AC-3 at 440 V |
|
maximum operating rate |
25 cyc/h |
|
rated duty |
Continuous conforming to IEC 60947-4-1 |
|
connections – terminals |
Screw clamp terminals 2 cable(s) 1…6 mm² solid Screw clamp terminals 2 cable(s) 1.5…6 mm² flexible without cable end Screw clamp terminals 2 cable(s) 1…4 mm² flexible with cable end |
|
tightening torque |
1.7 N.m on screw clamp terminals |
|
suitability for isolation |
Yes conforming to IEC 60947-1 |
|
phase failure sensitivity |
Yes conforming to IEC 60947-4-1 |
|
height |
89 mm |
|
width |
45 mm |
|
depth |
78.5 mm |
|
net weight |
0.26 kg |
standards |
EN/IEC 60947-2 EN/IEC 60947-4-1 CSA C22.2 No 60947-4-1 UL 60947-4-1 |
|
---|---|---|
product certifications |
IECEE CB Scheme UL CSA CCC EAC ATEX BV LROS (Lloyds register of shipping) DNV-GL RINA |
|
protective treatment |
TH |
|
IP degree of protection |
IP20 conforming to IEC 60529 |
|
IK degree of protection |
IK04 |
|
ambient air temperature for operation |
-20…60 °C |
|
ambient air temperature for storage |
-40…80 °C |
|
fire resistance |
960 °C conforming to IEC 60695-2-1 |
|
operating altitude |
2000 m |
Package 1 Weight |
227 g |
|
---|---|---|
Package 2 Weight |
5.778 kg |
|
Package 3 Weight |
106.404 kg |
Sustainable offer status |
Green Premium product |
|
---|---|---|
REACh Regulation |
REACh Declaration |
|
EU RoHS Directive |
Compliant EU RoHS Declaration |
|
Mercury free |
Yes |
|
RoHS exemption information |
Yes |
|
China RoHS Regulation |
China RoHS declaration Product out of China RoHS scope. Substance declaration for your information |
|
Environmental Disclosure |
Product Environmental Profile |
|
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Warranty |
18 months |
---|
There are no reviews yet.