device application |
Distribution |
|
---|---|---|
range |
Acti 9 |
|
product name |
Acti 9 iC60 |
|
product or component type |
Miniature circuit-breaker |
|
device short name |
IC60N |
|
poles description |
1P |
|
number of protected poles |
1 |
|
[In] rated current |
6 A |
|
network type |
AC DC |
|
trip unit technology |
Thermal-magnetic |
|
curve code |
C |
|
breaking capacity |
6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 10 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 15 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60898-1 Category A conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60947-2 EN 60898-1 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz |
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 % |
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz 7.5 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 27 kA 75 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 15 kA 75 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15 kA 75 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 6000 A 100 % conforming to EN 60898-1 – 230 V AC 50/60 Hz 6000 A 100 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 10 kA 100 % conforming to EN 60947-2 – 72 V DC 10 kA 100 % conforming to IEC 60947-2 – 72 V DC 15 kA 100 % conforming to EN 60947-2 – 12…60 V DC 15 kA 100 % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1 3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes |
|
control type |
Toggle |
|
local signalling |
Trip indicator |
|
mounting support |
DIN rail |
|
9 mm pitches |
2 |
|
height |
91 mm |
|
width |
18 mm |
|
depth |
78.5 mm |
|
net weight |
0.125 kg |
|
colour |
White |
|
mechanical durability |
20000 cycles |
|
electrical durability |
10000 cycles |
|
connections – terminals |
Double terminal (top or bottom) 1…25 mm² rigid Double terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection |
|
tightening torque |
2 N.m top or bottom |
|
earth-leakage protection |
Without |
IP degree of protection |
IP20 conforming to IEC 60529 IP20 conforming to EN 60529 |
|
---|---|---|
pollution degree |
3 |
|
overvoltage category |
IV |
|
tropicalisation |
2 |
|
relative humidity |
95 % at 55 °C |
|
ambient air temperature for operation |
-35…70 °C |
|
ambient air temperature for storage |
-40…85 °C |
Package 1 Weight |
0.114 kg |
---|
Sustainable offer status |
Green Premium product |
|
---|---|---|
REACh Regulation |
REACh Declaration |
|
EU RoHS Directive |
Compliant EU RoHS Declaration |
|
Mercury free |
Yes |
|
RoHS exemption information | ||
China RoHS Regulation |
China RoHS declaration Product out of China RoHS scope. Substance declaration for your information |
|
Environmental Disclosure |
Product Environmental Profile |
|
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Warranty |
18 months |
---|
There are no reviews yet.