| range of product | 
 Altivar 212 
 | 
|
|---|---|---|
| product or component type | 
 Variable speed drive 
 | 
|
| device short name | 
 ATV212 
 | 
|
| product destination | 
 Asynchronous motors 
 | 
|
| product specific application | 
 Pumps and fans in HVAC 
 | 
|
| assembly style | 
 With heat sink 
 | 
|
| network number of phases | 
 3 phases 
 | 
|
| motor power kW | 
 0.75 kW 
 | 
|
| motor power hp | 
 1 hp 
 | 
|
| [Us] rated supply voltage | 
 380…480 V – 15…10 % 
 | 
|
| supply voltage limits | 
 323…528 V 
 | 
|
| supply frequency | 
 50…60 Hz – 5…5 % 
 | 
|
| EMC filter | 
 Class C2 EMC filter integrated 
 | 
|
| line current | 
 1.4 A at 480 V 
1.7 A at 380 V  | 
| apparent power | 
 1.6 kVA at 380 V 
 | 
|
|---|---|---|
| prospective line Isc | 
 5 kA 
 | 
|
| continuous output current | 
 2.2 A at 380 V 
2.2 A at 460 V  | 
|
| maximum transient current | 
 2.4 A for 60 s 
 | 
|
| speed drive output frequency | 
 0.5…200 Hz 
 | 
|
| nominal switching frequency | 
 12 kHz 
 | 
|
| switching frequency | 
 6…16 kHz adjustable 
12…16 kHz with derating factor  | 
|
| speed range | 
 1…10 
 | 
|
| speed accuracy | 
 +/- 10 % of nominal slip 0.2 Tn to Tn 
 | 
|
| torque accuracy | 
 +/- 15 % 
 | 
|
| transient overtorque | 
 120 % of nominal motor torque +/- 10 % for 60 s 
 | 
|
| asynchronous motor control profile | 
 Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) 
Voltage/frequency ratio – Energy Saving, quadratic U/f Voltage/frequency ratio, 2 points Flux vector control without sensor, standard Voltage/frequency ratio, 5 points  | 
|
| regulation loop | 
 Adjustable PI regulator 
 | 
|
| motor slip compensation | 
 Not available in voltage/frequency ratio motor control 
Automatic whatever the load Adjustable  | 
|
| local signalling | 
 1 LED (red) for DC bus energized 
 | 
|
| output voltage | 
 <= power supply voltage 
 | 
|
| isolation | 
 Electrical between power and control 
 | 
|
| type of cable | 
 Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR 
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC  | 
|
| electrical connection | 
 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14 
L1/R, L2/S, L3/T: terminal 6 mm² / AWG 10  | 
|
| tightening torque | 
 1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T) 
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)  | 
|
| supply | 
 Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection 
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection  | 
|
| analogue input number | 
 2 
 | 
|
| analogue input type | 
 VIA switch-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits 
VIB configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0…6 probes, impedance: 1500 Ohm VIA switch-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 10 bits  | 
|
| sampling duration | 
 2 ms +/- 0.5 ms F discrete 
2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog  | 
|
| response time | 
 FM 2 ms, tolerance +/- 0.5 ms for analog output(s) 
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)  | 
|
| accuracy | 
 +/- 0.6 % (VIA) for a temperature variation 60 °C 
+/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C  | 
|
| linearity error | 
 VIA: +/- 0.15 % of maximum value for input 
VIB: +/- 0.15 % of maximum value for input FM: +/- 0.2 % for output  | 
|
| analogue output number | 
 1 
 | 
|
| analogue output type | 
 FM switch-configurable voltage 0…10 V DC, impedance: 7620 Ohm, resolution 10 bits 
FM switch-configurable current 0…20 mA, impedance: 970 Ohm, resolution 10 bits  | 
|
| discrete output number | 
 2 
 | 
|
| discrete output type | 
 Configurable relay logic: (FLA, FLC) NO – 100000 cycles 
Configurable relay logic: (FLB, FLC) NC – 100000 cycles Configurable relay logic: (RY, RC) NO – 100000 cycles  | 
|
| minimum switching current | 
 3 mA at 24 V DC for configurable relay logic 
 | 
|
| maximum switching current | 
 5 A at 250 V AC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R) 
5 A at 30 V DC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R) 2 A at 250 V AC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R)  | 
|
| discrete input type | 
 F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm 
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm  | 
|
| discrete input logic | 
 Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1) 
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)  | 
|
| acceleration and deceleration ramps | 
 Automatic based on the load 
Linear adjustable separately from 0.01 to 3200 s  | 
|
| braking to standstill | 
 By DC injection 
 | 
|
| protection type | 
 Overheating protection: drive 
Thermal power stage: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply overvoltage and undervoltage: drive Line supply undervoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor With PTC probes: motor  | 
|
| dielectric strength | 
 3535 V DC between earth and power terminals 
5092 V DC between control and power terminals  | 
|
| insulation resistance | 
 >= 1 mOhm 500 V DC for 1 minute 
 | 
|
| frequency resolution | 
 Display unit: 0.1 Hz 
Analog input: 0.024/50 Hz  | 
|
| communication port protocol | 
 Modbus 
METASYS N2 APOGEE FLN LonWorks BACnet  | 
|
| connector type | 
 1 open style 
1 RJ45  | 
|
| physical interface | 
 2-wire RS 485 
 | 
|
| transmission frame | 
 RTU 
 | 
|
| transmission rate | 
 9600 bps or 19200 bps 
 | 
|
| data format | 
 8 bits, 1 stop, odd even or no configurable parity 
 | 
|
| type of polarization | 
 No impedance 
 | 
|
| number of addresses | 
 1…247 
 | 
|
| communication service | 
 Read device identification (43) 
Time out setting from 0.1 to 100 s Write single register (06) Write multiple registers (16) 2 words maximum Monitoring inhibitable Read holding registers (03) 2 words maximum  | 
|
| option card | 
 Communication card for LonWorks 
 | 
|
| operating position | 
 Vertical +/- 10 degree 
 | 
|
| width | 
 107 mm 
 | 
|
| height | 
 143 mm 
 | 
|
| depth | 
 150 mm 
 | 
|
| net weight | 
 2 kg 
 | 
|
| power dissipation in W | 
 55 W 
 | 
|
| air flow | 
 19 m3/h 
 | 
|
| functionality | 
 Mid 
 | 
|
| specific application | 
 HVAC 
 | 
|
| IP degree of protection | 
 IP21 
 | 
|
| Variable speed drive application selection | 
 Compressor for scroll Building – HVAC 
Fan Building – HVAC Pump Building – HVAC  | 
|
| Motor power range AC-3 | 
 0.55…1 kW at 380…440 V 3 phases 
0.55…1 kW at 480…500 V 3 phases  | 
|
| motor starter type | 
 Variable speed drive 
 | 
| electromagnetic compatibility | 
 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11  | 
|
|---|---|---|
| pollution degree | 
 2 conforming to IEC 61800-5-1 
 | 
|
| IP degree of protection | 
 IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 
IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 IP21 conforming to EN/IEC 61800-5-1 IP21 conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529  | 
|
| vibration resistance | 
 1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6 
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8  | 
|
| shock resistance | 
 15 gn for 11 ms conforming to IEC 60068-2-27 
 | 
|
| environmental characteristic | 
 Classes 3C1 conforming to IEC 60721-3-3 
Classes 3S2 conforming to IEC 60721-3-3  | 
|
| noise level | 
 51 dB conforming to 86/188/EEC 
 | 
|
| operating altitude | 
 1000…3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m 
<= 1000 m without derating  | 
|
| relative humidity | 
 5…95 % without condensation conforming to IEC 60068-2-3 
5…95 % without dripping water conforming to IEC 60068-2-3  | 
|
| ambient air temperature for operation | 
 -10…40 °C (without derating) 
40…50 °C (with derating factor)  | 
|
| ambient air temperature for storage | 
 -25…70 °C 
 | 
|
| standards | 
 EN 55011 class A group 1 
EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C1 EN 61800-3 category C3 IEC 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 EN 61800-3 environments 1 category C1 UL Type 1 IEC 61800-3 category C2 EN 61800-3 IEC 61800-3 IEC 61800-3 environments 1 category C1 EN 61800-3 category C2 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 category C3 EN 61800-3 environments 2 category C3 IEC 61800-3 environments 1 category C3 EN 61800-5-1  | 
|
| product certifications | 
 UL 
NOM 117 CSA C-Tick  | 
|
| marking | 
 CE 
 | 
| Package 1 Weight | 
 1.937 kg 
 | 
|
|---|---|---|
| Package 2 Weight | 
 65.11 kg 
 | 
| Sustainable offer status | 
 Green Premium product 
 | 
|
|---|---|---|
| REACh Regulation | 
 REACh Declaration 
 | 
|
| EU RoHS Directive | 
 Pro-active compliance (Product out of EU RoHS legal scope) 
EU RoHS Declaration  | 
|
| Mercury free | 
 Yes 
 | 
|
| RoHS exemption information | 
 Yes 
 | 
|
| China RoHS Regulation | 
 China RoHS declaration 
 | 
|
| Environmental Disclosure | 
 Product Environmental Profile 
 | 
|
| Circularity Profile | 
 End of Life Information 
 | 
|
| WEEE | 
 The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins 
 | 
| Warranty | 
 18 months 
 | 
|---|

				





		
		
		
		
There are no reviews yet.