| device application |
Distribution |
|
|---|---|---|
| range |
Acti 9 |
|
| product name |
Acti 9 iC60 |
|
| product or component type |
Miniature circuit-breaker |
|
| device short name |
IC60N |
|
| poles description |
1P |
|
| number of protected poles |
1 |
|
| [In] rated current |
6 A |
|
| network type |
AC DC |
|
| trip unit technology |
Thermal-magnetic |
|
| curve code |
C |
|
| breaking capacity |
6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 10 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 15 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
| utilisation category |
Category A conforming to EN 60898-1 Category A conforming to IEC 60898-1 |
|
| suitability for isolation |
Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
| standards |
EN 60947-2 EN 60898-1 IEC 60898-1 IEC 60947-2 |
| network frequency |
50/60 Hz |
|
|---|---|---|
| magnetic tripping limit |
8 x In +/- 20 % |
|
| [Ics] rated service breaking capacity |
27 kA 75 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz 7.5 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 27 kA 75 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 15 kA 75 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15 kA 75 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 6000 A 100 % conforming to EN 60898-1 – 230 V AC 50/60 Hz 6000 A 100 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 10 kA 100 % conforming to EN 60947-2 – 72 V DC 10 kA 100 % conforming to IEC 60947-2 – 72 V DC 15 kA 100 % conforming to EN 60947-2 – 12…60 V DC 15 kA 100 % conforming to IEC 60947-2 – 12…60 V DC |
|
| limitation class |
3 conforming to EN 60898-1 3 conforming to IEC 60898-1 |
|
| [Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| [Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 |
|
| contact position indicator |
Yes |
|
| control type |
Toggle |
|
| local signalling |
Trip indicator |
|
| mounting support |
DIN rail |
|
| 9 mm pitches |
2 |
|
| height |
91 mm |
|
| width |
18 mm |
|
| depth |
78.5 mm |
|
| net weight |
0.125 kg |
|
| colour |
White |
|
| mechanical durability |
20000 cycles |
|
| electrical durability |
10000 cycles |
|
| connections – terminals |
Double terminal (top or bottom) 1…25 mm² rigid Double terminal (top or bottom) 1…16 mm² flexible |
|
| wire stripping length |
14 mm for top or bottom connection |
|
| tightening torque |
2 N.m top or bottom |
|
| earth-leakage protection |
Without |
| IP degree of protection |
IP20 conforming to IEC 60529 IP20 conforming to EN 60529 |
|
|---|---|---|
| pollution degree |
3 |
|
| overvoltage category |
IV |
|
| tropicalisation |
2 |
|
| relative humidity |
95 % at 55 °C |
|
| ambient air temperature for operation |
-35…70 °C |
|
| ambient air temperature for storage |
-40…85 °C |
| Package 1 Weight |
0.114 kg |
|---|
| Sustainable offer status |
Green Premium product |
|
|---|---|---|
| REACh Regulation |
REACh Declaration |
|
| EU RoHS Directive |
Compliant EU RoHS Declaration |
|
| Mercury free |
Yes |
|
| RoHS exemption information | ||
| China RoHS Regulation |
China RoHS declaration Product out of China RoHS scope. Substance declaration for your information |
|
| Environmental Disclosure |
Product Environmental Profile |
|
| WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
| Warranty |
18 months |
|---|







There are no reviews yet.