| range |
TeSys |
|
|---|---|---|
| product name |
TeSys D |
|
| product or component type |
Contactor |
|
| device short name |
LC1D |
|
| contactor application |
Resistive load Motor control |
|
| utilisation category |
AC-4 AC-1 AC-3 |
|
| poles description |
3P |
|
| power pole contact composition |
3 NO |
|
| [Ue] rated operational voltage |
Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC |
|
| [Ie] rated operational current |
9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
|
| motor power kW |
2.2 kW at 220…230 V AC 50/60 Hz (AC-3) 4 kW at 380…400 V AC 50/60 Hz (AC-3) 4 kW at 415…440 V AC 50/60 Hz (AC-3) 5.5 kW at 500 V AC 50/60 Hz (AC-3) 5.5 kW at 660…690 V AC 50/60 Hz (AC-3) 2.2 kW at 400 V AC 50/60 Hz (AC-4) |
|
| motor power HP (UL / CSA) |
1 hp at 230/240 V AC 50/60 Hz for 1 phase motors 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors |
|
| control circuit type |
AC at 50/60 Hz |
|
| [Uc] control circuit voltage |
230 V AC 50/60 Hz |
|
| auxiliary contact composition |
1 NO + 1 NC |
|
| [Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947 |
|
| overvoltage category |
III |
|
| [Ith] conventional free air thermal current |
25 A (at 60 °C) for power circuit 10 A (at 60 °C) for signalling circuit |
|
| Irms rated making capacity |
250 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
|
| rated breaking capacity |
250 A at 440 V for power circuit conforming to IEC 60947 |
|
| [Icw] rated short-time withstand current |
105 A 40 °C – 10 s for power circuit 210 A 40 °C – 1 s for power circuit 30 A 40 °C – 10 min for power circuit 61 A 40 °C – 1 min for power circuit 100 A – 1 s for signalling circuit 120 A – 500 ms for signalling circuit 140 A – 100 ms for signalling circuit |
|
| associated fuse rating |
10 A gG for signalling circuit conforming to IEC 60947-5-1 25 A gG at <= 690 V coordination type 1 for power circuit 20 A gG at <= 690 V coordination type 2 for power circuit |
|
| average impedance |
2.5 mOhm – Ith 25 A 50 Hz for power circuit |
|
| [Ui] rated insulation voltage |
Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified |
|
| electrical durability |
0.6 Mcycles 25 A AC-1 at Ue <= 440 V 2 Mcycles 9 A AC-3 at Ue <= 440 V |
|
| power dissipation per pole |
1.56 W AC-1 0.2 W AC-3 |
|
| Front cover |
With |
|
| mounting support |
Rail Plate |
|
| standards |
CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
|
| product certifications |
GOST BV LROS (Lloyds register of shipping) DNV CSA RINA CCC UL GL |
|
| connections – terminals |
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
|
| tightening torque |
Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 |
|
| operating time |
12…22 ms closing 4…19 ms opening |
|
| safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|
| mechanical durability |
15 Mcycles |
|
| maximum operating rate |
3600 cyc/h 60 °C |
| coil technology |
Without built-in suppressor module |
|
|---|---|---|
| control circuit voltage limits |
0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8…1.1 Uc (-40…60 °C):operational AC 50 Hz 0.85…1.1 Uc (-40…60 °C):operational AC 60 Hz 1…1.1 Uc (60…70 °C):operational AC 50/60 Hz |
|
| inrush power in VA |
70 VA 60 Hz cos phi 0.75 (at 20 °C) 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
|
| hold-in power consumption in VA |
7.5 VA 60 Hz cos phi 0.3 (at 20 °C) 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
|
| heat dissipation |
2…3 W at 50/60 Hz |
|
| auxiliary contacts type |
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 |
|
| signalling circuit frequency |
25…400 Hz |
|
| minimum switching current |
5 mA for signalling circuit |
|
| minimum switching voltage |
17 V for signalling circuit |
|
| non-overlap time |
1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
|
| insulation resistance |
> 10 MOhm for signalling circuit |
|
| contact compatibility |
M2 |
|
| compatibility code |
LC1D |
|
| motor power range |
1.1…2 kW at 200…240 V 3 phases 2.2…3 kW at 380…440 V 3 phases 4…6 kW at 380…440 V 3 phases 4…6 kW at 480…500 V 3 phases |
|
| motor starter type |
Direct on-line contactor |
|
| contactor coil voltage |
230 V AC standard |
| IP degree of protection |
IP20 front face conforming to IEC 60529 |
|
|---|---|---|
| protective treatment |
TH conforming to IEC 60068-2-30 |
|
| pollution degree |
3 |
|
| ambient air temperature for operation |
-40…60 °C 60…70 °C with derating |
|
| ambient air temperature for storage |
-60…80 °C |
|
| operating altitude |
0…3000 m |
|
| fire resistance |
850 °C conforming to IEC 60695-2-1 |
|
| flame retardance |
V1 conforming to UL 94 |
|
| mechanical robustness |
Vibrations contactor open: 2 Gn, 5…300 Hz Vibrations contactor closed: 4 Gn, 5…300 Hz Shocks contactor open: 10 Gn for 11 ms Shocks contactor closed: 15 Gn for 11 ms |
|
| height |
77 mm |
|
| width |
45 mm |
|
| depth |
86 mm |
|
| net weight |
0.32 kg |
| Package 1 Weight |
353 g |
|
|---|---|---|
| Package 2 Weight |
7.515 kg |
|
| Package 3 Weight |
128.74 kg |
| Sustainable offer status |
Green Premium product |
|
|---|---|---|
| REACh Regulation |
REACh Declaration |
|
| REACh free of SVHC |
Yes |
|
| EU RoHS Directive |
Compliant EU RoHS Declaration |
|
| Toxic heavy metal free |
Yes |
|
| Mercury free |
Yes |
|
| RoHS exemption information |
Yes |
|
| China RoHS Regulation |
China RoHS declaration Pro-active China RoHS declaration (out of China RoHS legal scope) |
|
| Environmental Disclosure |
Product Environmental Profile |
|
| Circularity Profile |
End of Life Information |
|
| WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
|
| PVC free |
Yes |
| Warranty |
18 months |
|---|







There are no reviews yet.