| range of product |
Altistart 01
|
|
|---|---|---|
| product or component type |
Soft starter
|
|
| product destination |
Asynchronous motors
|
|
| product specific application |
Simple machine
|
|
| device short name |
ATS01
|
|
| network number of phases |
3 phases
|
|
| [Us] rated supply voltage |
380…415 V – 10…10 %
|
|
| motor power kW |
4 kW, 3 phases at 380…415 V
|
|
| IcL starter rating |
9 A
|
|
| utilisation category |
AC-53B conforming to EN/IEC 60947-4-2
|
|
| current consumption |
45 A at nominal load
|
|
| type of start |
Start with voltage ramp
|
|
| power dissipation in W |
4 W at full load and at end of starting
94 W in transient state |
| assembly style |
With heat sink
|
|
|---|---|---|
| function available |
Integrated bypass
|
|
| supply voltage limits |
342…456 V
|
|
| supply frequency |
50…60 Hz – 5…5 %
|
|
| network frequency |
47.5…63 Hz
|
|
| output voltage |
<= power supply voltage
|
|
| [Uc] control circuit voltage |
Built into the starter
|
|
| starting time |
1 s / 100
5 s / 20 10 s / 10 Adjustable from 1 to 10 s |
|
| deceleration time symb |
Adjustable from 1 to 10 s
|
|
| starting torque |
30…80 % of starting torque of motor connected directly on the line supply
|
|
| discrete input type |
Logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
|
|
| discrete input voltage |
24…40 V
|
|
| discrete input logic |
Positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA
|
|
| discrete output current |
2 A DC-13
3 A AC-15 |
|
| discrete output type |
Open collector logic LO1 end of starting signal
Relay outputs R1A, R1C NO |
|
| discrete output voltage |
24 V (voltage limits: 6…30 V) open collector logic
|
|
| minimum switching current |
10 mA at 6 V DC for relay outputs
|
|
| maximum switching current |
Relay outputs: 2 A at 250 V AC cos phi = 0.5 and L/R = 20 ms inductive load
Relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load |
|
| display type |
1 LED (green) for starter powered up
1 LED (yellow) for nominal voltage reached |
|
| tightening torque |
0.5 N.m
1.9…2.5 N.m |
|
| electrical connection |
4 mm screw clamp terminal – rigid 1 1…10 mm² AWG 8 power circuit
Screw connector – rigid 1 0.5…2.5 mm² AWG 14 control circuit 4 mm screw clamp terminal – rigid 2 1…6 mm² AWG 10 power circuit Screw connector – rigid 2 0.5…1 mm² AWG 17 control circuit Screw connector – flexible with cable end 1 0.5…1.5 mm² AWG 16 control circuit 4 mm screw clamp terminal – flexible without cable end 1 1.5…10 mm² AWG 8 power circuit Screw connector – flexible without cable end 1 0.5…2.5 mm² AWG 14 control circuit 4 mm screw clamp terminal – flexible with cable end 2 1…6 mm² AWG 10 power circuit 4 mm screw clamp terminal – flexible without cable end 2 1.5…6 mm² AWG 10 power circuit Screw connector – flexible without cable end 2 0.5…1.5 mm² AWG 16 control circuit |
|
| marking |
CE
|
|
| operating position |
Vertical +/- 10 degree
|
|
| height |
124 mm
|
|
| width |
45 mm
|
|
| depth |
131 mm
|
|
| net weight |
0.42 kg
|
|
| compatibility code |
ATS01N2
|
|
| Motor power range AC-3 |
4…6 kW at 380…440 V 3 phases
|
|
| motor starter type |
Soft starter
|
| electromagnetic compatibility |
Conducted and radiated emissions level B conforming to CISPR 11
Conducted and radiated emissions level B conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-12 Electrostatic discharge level 3 conforming to IEC 61000-4-2 EMC immunity conforming to EN 50082-1 EMC immunity conforming to EN 50082-2 Harmonics conforming to IEC 1000-3-2 Harmonics conforming to IEC 1000-3-4 Immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Micro-cuts and voltage fluctuation conforming to IEC 61000-4-11 Voltage/current impulse level 3 conforming to IEC 61000-4-5 |
|
|---|---|---|
| standards |
EN/IEC 60947-4-2
|
|
| product certifications |
GOST
B44.1-96/ASME A17.5 for starter wired to the motor delta terminal CCC CSA C-Tick UL |
|
| IP degree of protection |
IP20
|
|
| pollution degree |
2 conforming to EN/IEC 60947-4-2
|
|
| vibration resistance |
1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f= 3…13 Hz) conforming to EN/IEC 60068-2-6 |
|
| shock resistance |
15 gn for 11 ms conforming to EN/IEC 60068-2-27
|
|
| relative humidity |
5…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
|
|
| ambient air temperature for operation |
-10…40 °C (without derating)
40…50 °C (with current derating of 2 % per °C) |
|
| ambient air temperature for storage |
-25…70 °C conforming to EN/IEC 60947-4-2
|
|
| operating altitude |
<= 1000 m without derating
> 1000 m with current derating of 2.2 % per additional 100 m |
| Package 1 Weight |
535 g
|
|---|
| REACh Regulation |
REACh Declaration
|
|
|---|---|---|
| REACh free of SVHC |
Yes
|
|
| EU RoHS Directive |
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration |
|
| Toxic heavy metal free |
Yes
|
|
| Mercury free |
Yes
|
|
| RoHS exemption information |
Yes
|
|
| China RoHS Regulation |
China RoHS declaration
|
|
| WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
| Warranty |
18 months
|
|---|







There are no reviews yet.