Specifications
- Measurement Range
- Fieldbus (pH): Four AI blocks assigned to pH, temperature, reference impedance, and glass impedance.
Fieldbus (ORP): Three AI blocks assigned to ORP, temperature, and reference impedance.
- Ambient Temperature
- Fieldbus (pH and ORP): Execution time 75 msec. One PID block; execution time 150 msec.
Device type 4085. Device revision 1. Certified to ITK 4.5.
- Power Supply
- Minimum power supply voltage is 12 Vdc. Maximum power supply voltage is 42.4 Vdc (30 Vdc for intrinsically safe operation). Power supply voltage should cover the voltage drop on the cable plus the external load resistor required for HART communications (250 Ω minimum).
- Certifications/Approvals
- For details, see specifications for the measurement of interest.
- Enclosure Rating
- Cast aluminum containing less than 6% magnesium, with epoxy polyester coating. NEMA 4X (IP65). Neoprene O-ring cover seals.
- Weight
- 10 lb/11 lb (4.5/5.0 kg)
Features
- Robust explosion-proof design constructed with heavy duty cast aluminum.
- Faster installation using Quick Start programming
- Intrinsically safe, non-incendive, and explosion-proof hazardous area location approvals
- Visibility of process parameters by utilizing HART or Foundation Fieldbus digital communications
- Effortlessly connect with PLCs and DCS’ by choosing the HART or FOUNDATION fieldbus communication options.
There are no reviews yet.