Specifications
- Port Diameters
- Supply port: 19 mm (0.75 inch)
Exhaust Port: 19 mm (0.75 inch)
- Input Signal
- Positioner output
- Maximum Input Signal Pressure
- 10.3 bar (150 psig)
- Input to Output Pressure Ratio
- Fixed at 1 to 1
- Supply Pressure Ranges
- Maximum pressure must not exceed 10.3 bar (150 psig)
- Operating Temperature
- -40 to 71 C (-40 to 160 F)
- Maximum Flow Coefficients
- Supply: 9.5 Cv
Exhaust 9.5 Cv
C1: 35
Xt: 0.77
- Connections
- Input signal: 1/4 NPT
Supply: 1 NPT
Output: 1 or 1-1/4 NPT
- Hazardous Area Classification
- Complies with the requirements of ATEX Group II Category 2 Gas and Dust
- Declaration of SEP
- Fisher Controls International LLC declares this product to be in compliance with Article 3 paragraph 3 of the Pressure Equipment Directive (PED) 97 / 23 /EC. It was designed and manufactured in accordance with Sound Engineering Practice (SEP) and cannot
- Approximate Weight
- Aluminum: 3.6 kg (8 lbs)
Stainless Steel: 10.8 kg (24 lbs)
- Other Configurations
- Contact your local Emerson business partner or sales office to learn about additional specifications or options for this product.
Features
- Fast Response: The SS-263 delivers high-volume output for fast stroking speeds when responding to large input signal changes and low-volume output when responding to small input changes.
- High capacity: Flow capacities of roughly three times higher than the 2625 booster result in the need for fewer fittings, tubing, and units.
- Noise Attenuation: Exhaust is passed through specially-designed passages to reduce the amountof ambient noise that is generated.
- Adjustable Response: The integral bypass restriction allows the booster to be easily and readily tuned to operate under small or large input signal changes.
- Auxiliary Supply Connections: Supply air is readily available through two 1/4 NPT connections that are built into both sides of the unit for use with a Fisher 377 trip valve or other accessory.
- 3 in 1 Connection: This special connection can provide any of the following connections, if needed: 1/4 NPT diagnostic connection for easy testing, 1/4 NPT actuator bypass assembly connection foruse on an actuator with a handwheel, and 3/4 NPT connection
- Soft-Seated Construction: Soft seated exhaust and supply valves provide for bubble tight shutoff toreduce unnecessary air consumption and ensure fail mode upon loss of plant air.
- Robust Mounting: Flanged-style actuator mounting provides ease of maintenance, simplifiedtubing, compactness, and high vibration resistance.