ATV212H075N4

Schneider Electric

Variable speed drive ATV212

0.75kW – 1hp – 480V – 3ph – EMC – IP21

 

 

Compare
Main
range of product
Altivar 212
product or component type
Variable speed drive
device short name
ATV212
product destination
Asynchronous motors
product specific application
Pumps and fans in HVAC
assembly style
With heat sink
network number of phases
3 phases
motor power kW
0.75 kW
motor power hp
1 hp
[Us] rated supply voltage
380…480 V – 15…10 %
supply voltage limits
323…528 V
supply frequency
50…60 Hz – 5…5 %
EMC filter
Class C2 EMC filter integrated
line current
1.4 A at 480 V
1.7 A at 380 V
Complementary
apparent power
1.6 kVA at 380 V
prospective line Isc
5 kA
continuous output current
2.2 A at 380 V
2.2 A at 460 V
maximum transient current
2.4 A for 60 s
speed drive output frequency
0.5…200 Hz
nominal switching frequency
12 kHz
switching frequency
6…16 kHz adjustable
12…16 kHz with derating factor
speed range
1…10
speed accuracy
+/- 10 % of nominal slip 0.2 Tn to Tn
torque accuracy
+/- 15 %
transient overtorque
120 % of nominal motor torque +/- 10 % for 60 s
asynchronous motor control profile
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Voltage/frequency ratio – Energy Saving, quadratic U/f
Voltage/frequency ratio, 2 points
Flux vector control without sensor, standard
Voltage/frequency ratio, 5 points
regulation loop
Adjustable PI regulator
motor slip compensation
Not available in voltage/frequency ratio motor control
Automatic whatever the load
Adjustable
local signalling
1 LED (red) for DC bus energized
output voltage
<= power supply voltage
isolation
Electrical between power and control
type of cable
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
electrical connection
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 6 mm² / AWG 10
tightening torque
1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T)
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
supply
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection
analogue input number
2
analogue input type
VIA switch-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0…6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 10 bits
sampling duration
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
response time
FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
accuracy
+/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °C
linearity error
VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for output
analogue output number
1
analogue output type
FM switch-configurable voltage 0…10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0…20 mA, impedance: 970 Ohm, resolution 10 bits
discrete output number
2
discrete output type
Configurable relay logic: (FLA, FLC) NO – 100000 cycles
Configurable relay logic: (FLB, FLC) NC – 100000 cycles
Configurable relay logic: (RY, RC) NO – 100000 cycles
minimum switching current
3 mA at 24 V DC for configurable relay logic
maximum switching current
5 A at 250 V AC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R)
discrete input type
F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
discrete input logic
Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
acceleration and deceleration ramps
Automatic based on the load
Linear adjustable separately from 0.01 to 3200 s
braking to standstill
By DC injection
protection type
Overheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motor
dielectric strength
3535 V DC between earth and power terminals
5092 V DC between control and power terminals
insulation resistance
>= 1 mOhm 500 V DC for 1 minute
frequency resolution
Display unit: 0.1 Hz
Analog input: 0.024/50 Hz
communication port protocol
Modbus
METASYS N2
APOGEE FLN
LonWorks
BACnet
connector type
1 open style
1 RJ45
physical interface
2-wire RS 485
transmission frame
RTU
transmission rate
9600 bps or 19200 bps
data format
8 bits, 1 stop, odd even or no configurable parity
type of polarization
No impedance
number of addresses
1…247
communication service
Read device identification (43)
Time out setting from 0.1 to 100 s
Write single register (06)
Write multiple registers (16) 2 words maximum
Monitoring inhibitable
Read holding registers (03) 2 words maximum
option card
Communication card for LonWorks
operating position
Vertical +/- 10 degree
width
107 mm
height
143 mm
depth
150 mm
net weight
2 kg
power dissipation in W
55 W
air flow
19 m3/h
functionality
Mid
specific application
HVAC
IP degree of protection
IP21
Variable speed drive application selection
Compressor for scroll Building – HVAC
Fan Building – HVAC
Pump Building – HVAC
Motor power range AC-3
0.55…1 kW at 380…440 V 3 phases
0.55…1 kW at 480…500 V 3 phases
motor starter type
Variable speed drive
Environment
electromagnetic compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
pollution degree
2 conforming to IEC 61800-5-1
IP degree of protection
IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1
IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP21 conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
vibration resistance
1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8
shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
environmental characteristic
Classes 3C1 conforming to IEC 60721-3-3
Classes 3S2 conforming to IEC 60721-3-3
noise level
51 dB conforming to 86/188/EEC
operating altitude
1000…3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
<= 1000 m without derating
relative humidity
5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
ambient air temperature for operation
-10…40 °C (without derating)
40…50 °C (with derating factor)
ambient air temperature for storage
-25…70 °C
standards
EN 55011 class A group 1
EN 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C2
EN 61800-3 environments 2 category C1
EN 61800-3 category C3
IEC 61800-3 environments 1 category C2
EN 61800-3 environments 1 category C2
IEC 61800-3 environments 2 category C3
IEC 61800-5-1
EN 61800-3 environments 1 category C1
UL Type 1
IEC 61800-3 category C2
EN 61800-3
IEC 61800-3
IEC 61800-3 environments 1 category C1
EN 61800-3 category C2
IEC 61800-3 environments 2 category C1
IEC 61800-3 environments 2 category C2
IEC 61800-3 category C3
EN 61800-3 environments 2 category C3
IEC 61800-3 environments 1 category C3
EN 61800-5-1
product certifications
UL
NOM 117
CSA
C-Tick
marking
CE
Packing Units
Package 1 Weight
1.937 kg
Package 2 Weight
65.11 kg
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Contractual warranty
Warranty
18 months
Brands

Schneider Electric

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “ATV212H075N4”